The most versatile and intelligent Multifunction meter for measuring all the basic electrical parameters along with energy and power.
Sr. No. | Parameters & Options |
|
|
---|---|---|---|
01 | Volts R-N | Direct Voltage Input : Up to 300V L-N Burden : 0.5VA Secondary Voltage Input : 63.5V* |
|
02 | Volts Y-N | ||
03 | Volts B-N | ||
04 | Volts RY | Direct Voltage Input : Up to 500V L-L Burden : 0.5VA Secondary Voltage Input : 110V* |
|
05 | Volts YB | ||
06 | Volts BR | ||
07 | Current R | Secondary Current Input : 5A or 1A (To be specified at thetime of Ordering) CT Primary : Site Selectable Range of Reading : 0 – 4000A Burden : < 1.0VA Overload(Through CT) : 5A CT = 6A RMS Continuous 1A CT = 1.2A RMS Continuous (Whole Current) : 120% of Imax continuous. |
|
08 | Current Y | ||
09 | Current B | ||
10 | Frequency | 45 to 55 Hz, Accuracy : 0.3% of Reading | |
11 | KWh | Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.0S as per IS13779. |
|
12 | KVARh | Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.5% of Reading (Between 0.5 Lag to 0.8 Lead) |
|
13 | KVAh | Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.0% of Reading |
|
14 | System PF | Accuracy : 1% of Reading (IPFI>0.5) Range of Reading : 0.05 to 1.00 Lag/Lead |
|
15 | System KVA | Accuracy : 1.0% of Reading | |
16 | System KW | Accuracy : 1.0% of Reading (Between 0.5 Lag to 0.8 Lead) |
|
17 | System KVAR | Accuracy : 1.5% of Reading (Between 0.5 Lag to 0.8 Lead) |
|
18 | DISPLAY | 0.4” Red Seven Segment. | |
19 | RS485 | For Integration with EMS/SCADA | |
20 | Bezel | 96x96 mm | DIN enclosure |
21 | Depth | 55 mm |