The Power Pro from Trinity is an easy-to-use, cost effective electrical power meter that offers all the basic measurement capabilities required to monitor an electrical installation. In addition to measuring the instantaneous parameters, it also measures accurately all three energies, and also demand, thus helping to measure and control energy costs.
Over the basic metering, it optionally provides two relay outputs, RS485 port supporting MODBUS RTU protocol, dual source metering and THD measurements.
The relays are site programmable for parameter of action, and the value on which to operate.
The CT primary and secondary, PT ratio and installation type are site selectable, thus making it possible to use the meter in all types of three phase installations.
Parameter | |||
---|---|---|---|
Type | Name | Statistics | |
Input | Supply | Three Phases and Neutral of a 3P4W system / Three Phases of a 3P3W system | |
Voltage | Direct Voltage Input : Up to 500V L-L, Up to 300V L-N PT Ratio: Site Selectable Burden: 0.5VA |
||
Current | Secondary Current Input: 5A or 1A (Site Selectable) CT Ratio: Site Selectable Range of Reading : 5 - 5000A Burden: < 1.0V Overload: 5A CT = 6A RMS Continuous 1A CT = 1.2A RMS Continuous |
||
PowerSupply | Auxiliary Supply: 90 - 480 VAC, 50-60 Hz. | ||
Output | Relay | Two. Individually Field Programmable. Switching Voltage: Max. 250 VAC Switching Power : Max. 1000W Expected Mechanical Life: >10 x 106 switching operations. Expected Electrical Life : >4 x 106 switching operations. @(Load = 200VA, Coscp = 0.5) |
|
Measurment | True RMSBasic Parameters | Voltag(Volts L-N& L-L) | VL-N - Accuracy : 0.5% of Reading VL-L - Accuracy : 1.0% of Reading |
Current(Amps IR,IY, IB) | Accuracy : 0.25% of Reading | ||
LineFrequency | 45 to 55 Hz, Accuracy: 0.3% of Reading | ||
Power | ActivePower (P) | Accuracy: 1% of Reading(For IPFI>0.5) | |
ReactivePower (Q) | Accuracy: 1.5% of Reading (Between 0.5 Lag to 0.8 Lead) |
||
ApparentPower (S) | Accuracy: 1%% of Reading | ||
PoweFactor | For Individual phases and System Accuracy: 1.0% of Reading (IPFI20.5) Range of Reading: 0.05 to 1.00 Lag/Lead |
||
Energy | TotalActiveEnergy(KWh) | Range of Reading: 0 to 9999999.9 KWh Accuracy: 1.0s as per IS13779 |
|
TotalApparentEnerg(KVAh) | Range of Reading: 0 to 9999999.9 KWh Accuracy: 1.0% of Reading |
||
TotalApparentEnergy(KVARh) | Range of Reading: 0 to 9999999.9 KWh Accuracy: 1.5% of Reading |
||
PowerQuality | THD for each Voltage (Optional) | ||
THD for each Current (Optional) | |||
Demand | KVA/ KWDemand | Site Selectable. Demand Interval 15/30 Min. Also site selectable | |
Max.Demand | Max. Value reached only. No time & date stamp | ||
Dimensions | Bezel | 96 X 96 mm | |
Miscellaneous | PanelCutout | 92 X 92 mm | |
Depth ofinstallation | 55 mm | ||
Display | 16 X 1 Backlight LCD or 128 X 64 Graphical Backlight LCD(To be specified at the time of Ordering) | ||
Operatintemp | 10°C to 50°C | ||
Weight | 0.35 Kgs (Approx.) | ||
Min.OperatingCurrent | 0.4% to 120% of CT primary | ||
Comm. | RS485 | Modbus-RTU protocol |
Input | Supply | Three Phases and Neutral of a 3P4W system / Three Phases of a 3P3W system |
Input | Voltage | Direct Voltage Input : Up to 500V L-L, Up to 300V L-N PT Ratio: Site Selectable Burden: 0.5VA |
Input | Current | Secondary Current Input: 5A or 1A (Site Selectable) CT Ratio: Site Selectable Range of Reading : 5 - 5000A Burden: < 1.0V Overload: 5A CT = 6A RMS Continuous 1A CT = 1.2A RMS Continuous |
Input | Power Supply | Auxiliary Supply: 90 - 480 VAC, 50-60 Hz |
Measurement - True RMS Basic Parameters | Voltage(Volts L-N & L-L) | VL-N - Accuracy : 0.5% of Reading VL-L - Accuracy : 1.0% of Reading |
Measurement - True RMS Basic Parameters | Current(Amps IR, IY, IB) | Accuracy : 0.25% of Reading |
Measurement - True RMS Basic Parameters | Line Frequency | 45 to 55 Hz, Accuracy : 0.3% of Reading |
Measurement - Power | Active Power (P) | Accuracy : 1% of Reading (For IPFI > 0.5) |
Measurement - Power | Reactive Power (Q) | Accuracy : 1.5% of Reading (Between 0.5 Lag to 0.8 Lead) |
Measurement - Power | Apparent Power (S) | Accuracy : 1% of Reading |
Measurement - Power | Power Factor | For Individual phases and System Accuracy : 1.0% of Reading (IPFI ≥ 0.5) Range of Reading : 0.05 to 1.00 Lag/Lead |
Measurment - Energy | Total Active Energy (KWh) | Range of Reading : 0 to 9999999.9 KWh Accuracy : 1.0s as per IS13779 |
Measurment - Energy | Total Apparent Energy (KVAh) | Range of Reading : 0 to 9999999.9 KVAh Accuracy : 1.0% of Reading |
Measurment - Energy | Total Apparent Energy (KVARh) | Range of Reading : 0 to 9999999.9 KVARh Accuracy : 1.5% of Reading |
Measurment - PowerQuality | THD for each Voltage (Optional) | |
Measurment - PowerQuality | THD for each Current (Optional) | |
Measurment - Demand | KVA/ KWDemand | Site Selectable. Demand Interval 15/30 Min. Also site selectable |
Measurment - Demand | Max.Demand | Max. Value reached only. No time & date stamp |
Measurment - Dimensions | Bezel | 96 X 96 mm |
Miscellaneous - Dimensions | PanelCutout | 92 X 92 mm |
Miscellaneous - Dimensions | Depth ofinstallation | 55 mm |
Miscellaneous | Display | 16 X 1 Backlight LCD or 128 X 64 Graphical Backlight LCD(To be specified at the time of Ordering) |
Miscellaneous | Operatintemp | 10°C to 50°C |
Miscellaneous | Weight | 0.35 Kgs (Approx.) |
Miscellaneous | Min.OperatingCurrent | 0.4% to 120% of CT primary |
Miscellaneous - Comm. | RS485 | Modbus-RTU protocol |